PowerPanel™ Business Edition
37
z Verify that firewall settings. Port 3052(UDP/TCP), port 53568(TCP), port 162(UDP) and port 53566(UDP)
should be unblocked. The Client communicates with the power device on these ports. The installer will
automatically configure Windows firewall to allow PowerPanel
®
Applications to access through firewall.
The following messages may be displayed:
z Detecting X.X.X.X is unsuccessful. The power device may not be available on the local network
because it is either turned off or the specified IP address is not the one used by this device. Make sure
that the IP address is accurate and the power device is operating then click Retry to initiate outlet
detection again.
The USB cable or serial port between the Agent and the UPS may not be connected or the UPS
RMCARD is installed improperly. Check the cable connections and the installation of the RMCARD and
then click Retry to initiate outlet detection again.
z The device address has changed to X.X.X.X. Client updated using the Auto Configure option. The
IP address of the power device has changed to a new one, and the Client has been configured to match
the new IP Address.
z Network communication can’t be established. Make sure the devices network configuration is
accurate. The Client never establishes the communication with device due to improper network
configuration on the device. See Troubleshooting the Client’s inability to communicate
with the
power device section for more details to resolve this condition.
z Network communication lost. Make sure the devices network configuration is accurate. The
network communication between the Client and the device has been lost. The device could be turned off
and the Client is no longer aware of the condition from the device. See Troubleshooting the Client’s
inability to communicate with the power device section for more details to resolve this condition.
z Can’t fetch the outlet information. Make sure that the device local communication is connected.
The USB cable or serial port between the Agent and the UPS may not be connected or the UPS
RMCARD could be plugged improperly. Verify the local communication is connected property.
z The assigned outlet is in use. Please choose another outlet. Indicates the assigned outlet is in used
by another piece of equipment or computer. In order for the Client to perform a graceful shutdown, it is
recommended to change to another outlet which is not in use.
z The assigned outlet is off. Please choose another outlet. The outlet assigned is not supplying power,
and the wrong outlet may have been identified. Verify the correct outlet is selected. .
z The assigned outlet has a turn off pending. The system will be shutdown soon. The outlet being
used by the Client computer will be switched off and will stop supplying power to the Client computer
after the delay is finished. Save all unsaved files and shut down the hosted computer as soon as
possible.
z System may not shutdown properly because the off-delay is too short. The Client detected the
connected outlet has insufficient time for the hosted computer to perform a shutdown. The off-delay may
be extended in the PDU web interface.